Mon Jun 18 15:44:52 2018
Mon Jun 18 15:44:52 2018
UFA/UMA710-ISO

UFA/UMA710-ISO

工厂定制模块系列用于切换 (t <= 0.5 s) 2个电源 (AV/SV resp. SV/UPS),并且产品用于医疗场所的IT系统监视。报警指示和显示操作单元上的状态显示和报警文本通过总线技术实现。模块适用于所有通用DIN导轨系统的安装。

  • 特征
  • 应用
  • 附件
  • 订货信息
  • 下载
  • Automatic changeover and monitoring device ATICS® including monitoring of i.e.:
    - Voltage of incoming supply of Line 1 and 2
    - Output voltage
    - Correct operating times
    - Changeover times
    - Functional safety as to IEC 61508 (SIL2)
  • Uninterruptable testing and exchange upon optional bypass switch (bypass recommended)
  • with insulation fault locator EDS151
  • Variable changeover period t≤0.5 ... 15s
  • Exchange of information by means of bus technology
  • Connection facility for remote alarm indicator and operator panels TM800 / MK800 / MK2430
  • Short delivery time
  • Time and cost-saving handling by use of prewired distribution boards
  • Screw less termination on all of the in- and outgoing connections
  • Designed in accordance with the requirements of applicable standards
  • Voluntary certification of changeover device by the independent German technical service, testing and inspection organization (TÜV)

 

版本 UFA/UMA710-ISO

UFA710-2-xx-ISO, …-BP
TypeCircuitsNominal current (AC3) changeover moduleMax. admissible current accord. to DIN VDE 0100-710Upstream fuse max.Consumption ca.
UFA710-2-63-ISO-06-B16663A63A80A, gG16W
UFA710-2-63-ISO-12-B161263A63A80A, gG17W
UFA710-2-63-ISO-18-B161863A63A80A, gG18W
UFA710-2-63-ISO-24-B162463A63A80A, gG19W
UFA710-2-63-ISO-BP-06-B16663A63A80A, gG16W
UFA710-2-63-ISO-BP -12-B161263A63A80A, gG17W
UFA710-2-63-ISO-BP -18-B161863A63A80A, gG18W
UFA710-2-63-ISO-BP -24-B162463A63A80A, gG19W
UFA710-2-80-ISO-06-B16680A80A100A, gG28W
UFA710-2-80-ISO-12-B161280A80A100A, gG29W
UFA710-2-80-ISO-18-B161880A80A100A, gG30W
UFA710-2-80-ISO-24-B162480A80A100A, gG31W
UFA710-2-80-ISO-BP-06-B16680A80A100A, gG28W
UFA710-2-80-ISO-BP -12-B161280A80A100A, gG29W
UFA710-2-80-ISO-BP -18-B161880A80A100A, gG30W
UFA710-2-80-ISO-BP -24-B162480A80A100A, gG31W

UMA710-2-xx-ISO, ...-BP

TypeNominal current (AC3) changeover moduleMax. admissible current accord. to DIN VDE 0100-710Upstream fuse max.Consumption ca.
UMA710-2-63-ISO63A63A80A, gG16W
UMA710-2-80-ISO80A80A<100A, gG28W
UMA710-2-63-ISO-BP63A63A80A, gG19W
UMA710-2-80-ISO-BP80A80A100A, gG31W

UMA710-2-xx-ISO-xx-RF

TypeNominal current (AC3) changeover moduleMax. admissible current accord. to DIN VDE 0100-710Upstream fuse max.Consumption ca.
UMA710-2-63-ISO-RF63 A63 A80 A, gG22 W