LINETRAXX® RCMS150 series

LINETRAXX® RCMS150 series

  • 通过绝缘试验来替代定期检查
  • 交直流敏感型测量值采集,B型
  • 纯直流故障评估
  • 适用于密闭空间
  • 带BMS可视化数据的RS-485

6通道剩余电流监视仪RCMS150被设计用于接地系统的交流和直流故障电流的测量,设备采用六脉冲整流器或单向整流器的平滑处理,能够脱离负载上的绝缘故障。设备能够测量频率范围DC 0...2 kHz以及最大可达 I? = 500 mA的剩余电流。2组独立可调响应值允许区别预报警和报警。设备带RS-485接口,能够传输测量值和报警值。也可以通过此接口设置参数。

  • 特征
  • 应用
  • 附件
  • 订货信息
  • 下载
  • Continuous residual current monitoring in compliance with DGUV Vorschrift 3 (German Social Accident Insurance Regulation 3)
  • AC/DC sensitive residual current monitor type B with 6 channels K1…6 (each channel features 2 measuring channels: 1 x RMS, 1 x DC)
  • Ideal for applications with space limitations
  • Easy DIN rail or screw mounting to standard distribution panels
  • 2 separately adjustable response values (DC or RMS) per channel
  • Continuous self monitoring
  • Fully shielded measuring current transformers to avoid external influences due to magnetic fields that may cause disturbances
  • Compatible with Bender gateways of type COM465IP, CP9…
  • RCMS150 (RS-485 interface with BMS protocol)
    - Compatible with RCMS460/490 in a system setup
    - Address range 2…90, can be adjusted directly on the device
    - Up to 89 RCMS150 can be used on the bus
  • RCMS150-01 (RS-485 interface with Modbus RTU protocol)
    - Compatible with other Modbus RTU-capable device series from Bender, such as the RCMB300 series and RCMB13…-01 in a system setup
    - Address range 1…99, can be adjusted directly on the device via detent poten­tiometers
    - Address range 1…247, can be adjusted via the bus
    - Up to 247 RCMS150-01 can be used on the bus
  • The device RCMS150 series is suitable for measuring AC and DC fault currents up to IΔ = 500 mA in a frequency range of DC 0…2 kHz. The monitored circuit is rated for a voltage of 300 V and a load current of 32 A. The device can be operated at an altitude of up to 2000 m above mean sea level.

 

可选配件 LINETRAXX® RCMS150 series


DescriptionRCMS150RCMS150-01TypeArt. No.
Mounting clip for DIN rail mountingB91080110
Condition Monitor with integrated gatewayCOM465IP
CP907-I (flush-mounted enclosure)
CP907-I (control cabinet door mounting)
B95061065
B95061031
B95061032
RS-485 repeaterDI-1DLB95012047
Residual current monitoring system*-RCMS460-D-1
RCMS460-D-2
RCMS490-D-1
RCMS490-D-2
B94053001
B94053002
B94053005
B94053006
* In this case, no condition monitor/gateway is necessary
Suitable for measured value and alarm indication only, not suitable for parameter setting

版本 LINETRAXX® RCMS150 series


TypeNominal supply voltage UsProtocolArt. No.
RCMS150DC 24 VBMSB94053025
RCMS150-01DC 24 VModbus RTUB94053026

下载 LINETRAXX® RCMS150 series

分类

语言

分类 产品 语言 尺寸 下载